keling would like to show you a technical proposal for the design, manufacturing, supply, installation, and commissioning of a mobile containerized clean room system for the assembly of dust-sensitive electronic components.
Please find below a summary of our project requirements:
1. Project Overview
- Application: Electronics assembly (dust-sensitive components)
- Cleanroom type: Containerized, modular, relocatable
- Estimated total area: ~400 m²
2. Cleanroom Requirements
- General area: ISO Class 7
- Local zones (clean benches): ISO Class 5
- Cleanliness requirement: Under operational conditions (to be confirmed by supplier)
3. Container Configuration
- Approx. 16 × 40 ft High Cube containers
- Interconnected layout for process flow
- Each container to include:
- Personnel entry
- Gowning area
- Air shower
4. Environmental Conditions
- Temperature: 20–22 °C
- Relative Humidity: ≤ 20–25%
- Pressure: Positive (preferred)
5. Process Considerations
- Assembly of dust-sensitive electronic components
- Presence of ovens generating heat and particles
- 6. Scope of Request
We kindly request you to provide:
- Budgetary quotation (preferably itemized)
- Technical proposal including HVAC concept
- Preliminary layout drawings
- Estimated power consumption
- Project execution timeline
7. Additional Information Requested
Please also include:
- Recommended HVAC system (FFU or centralized AHU)
- Proposed air change rate and airflow concept
- Dehumidification method to achieve ≤25% RH
- Approach for handling heat and particle generation from ovens
- Cleanroom validation method (ISO 14644)
- Reference projects for similar containerized cleanrooms